400 kVA / 500 kVA / 625 kVA


Genset Prime Rating (kVA) * 400 500 625
Genset Prime Rating (KW) 320 400 500
Phase / Voltage (V) 3/415
Power Factor 0.8 (lagging)
Current (A) 556 695 869
Frequency (Hz)& RPM 50/1500
Governing class G2 G2 G2
Starting system 24 V DC Electrical
Fuel tank capacity (lit) 700 800
Genset dimensions w/o silencer (mm) (L x W x H) approx. 5000x1900x2302 5850 X 2000 X 2300
Genset Weight (kg) approx. 5200 5800 7500
Engine Specification
Make / Series Perkins
Engine Model 2206D-E13TAG3 2506D-E15TAG2 2806D-E18TAG 1A
Power Output# (Kw) 367 453 540
Aspiration Turbo Charged After Cooled
No. of cylinders 6
Bore x Stroke (mm) 130*157 137*171 145*183
Displacement (Lit) 12.5 15.2 18.1
Fuel consumption @ 75% load (lit/hr)^ 65.5 78.6 97
Fuel consumption @ 100% load (lit/hr)^ 90.5 101 130
Total lubrication system capacity (lit) 40 62 71
Lube oil consumption @ 100% load* 0.1% of fuel consumption
Lube oil change period (hrs.) 500
Radiator coolant capacity (lit) 51.4 48 55.6
Alternator
Make** CG/LS/Stamford
Enclosure Type IP23
Voltage regulation ±1%
Class of insulation Class H
Maximum Unbalanced Load across Phases 25%

 

Above specifications are subject to change without prior notice due to continuous product improvements.

  • All engines & alternators confirm to respective IS standards
  • All the genset specifications are as per ISO 8528 standard
  • Fuel - High Speed Diesel (HSD IS 1460:2005)
  • Considering 0.850 specific gravity of diesel 5% tolerance
  • Considering 0.89 specific gravity of oil
  • For Standby duty, contact Powerol authorized representative
  • All specifications are at standard NTP operating conditions
  • All the above gensets conform to the latest CPCB norms of <75 dbA