50 kVA / 62.5 kVA


PARAMETERS DG MODELS
Duty (Standby/ Prime) Prime Prime
50 HZ PRIME Rating(kVA) 50 kVA 62.5 kVA
Rated(kWe) 40 50
Engine Model 4725GMAC2 4905GMAC2
Power Factor (lagging) 0.8 0.8
Governing class G2 G2
Starting system 12 V DC Elec 12 V DC Elec
Intergrated Fuel Tank Capacity (lits) 185 185
Genset Dimension (LxWxH $$) (mm) Approx. 2400 X 1050 X 1523 2400 X 1050 X 1523
Genset Weight (Kg), Appx 1258 1293
Make Mahindra Mahindra
Power Output# (HP) 72 90
Aspiration Turbocharged & Intercooled Turbocharged & Intercooled
No of Cylinders 4 4
Bore x Stroke (mm) 94 x 115 96 x 122
Displacement (cc) 3192 3532
Fuel consumption @ 75% load (lit/hr) ^ 9.5 11.3
Fuel consumption @ 100% load (lit/hr) ^ 12.4 15.3
Lube oil specification SAE15W40 CI4 SAE15W40 CI4
Total Lube Oil capacity (lit) 10 10
Lube Oil Consumtion (lit/hr) $ 0.1% of Fuel Consumption
Lube oil change period (hrs.) 300 hrs. for Oil Top Up
600 hrs. for Oil change
Radiator coolant capacity (liter) 12 15
Alternator
Enclosure Type IP23
Voltage regulation ±1%
Class of insulation Class H
Maximum Unbalanced Load across Phases 25%

 

All Specifications are at Standard NTP operating conditions

  • Considering 0.845 Specific Gravity of diesel, +5 % Tolerance
  • Engine Power at 110 % load
  • Fuel -High Speed diesel (HSD IS 1460:2005)
  • Represent the Standby Ratings
  • Considering 0.89 Specific Gravity of Oil
  • Engine Power will have ± 5 % Tolerance
  • For CG only 3 Phase Configuration available
  • Height Without Silencer